Physical Specifications
Technical Specifications
Packaging & Dimensions:
|
||||||||||||||||||||||||||||||||||
The overall jacket diameter for 4/0 STR 15kV 133% URD is approximately 1.38 inches. For a single-conductor installation, a 2.5-inch to 3-inch conduit is standard. For a triplex configuration (three cables), a 4-inch or 5-inch conduit is recommended.
Because of the 1.38" diameter, a 4-inch conduit is the absolute minimum for triplex to avoid "jamming" and to maintain the NEC 40% fill limit. For long pulls with multiple bends, a 5-inch conduit may be required to ensure a safe installation.
Note on Conduit Sizing: These recommendations are based on standard NEC 40% fill guidelines for general informational purposes. Because factors such as pull length, total degrees of bends, and pulling tension vary by project, always consult with a licensed electrical engineer or project lead to verify final conduit specifications and ensure local code compliance.
This 4/0 AWG cable features 13 x #10 AWG solid bare copper neutral wires. These wires are helically applied and uniformly spaced over the insulation shield to provide 100% (Full) conductivity relative to the phase conductor, providing maximum grounding performance for high-load feeders.
15kV Aluminum URD (Underground Residential Distribution) cable is a medium-voltage cable used for primary underground power distribution at 15,000 volts or less. It features an aluminum conductor, solid or stranded, with Tree-Retardant Cross-Linked Polyethylene (TR-XLPE), rated for direct burial or duct installation in wet/dry locations.
RUS Accepted means this cable meets the technical and durability standards set by the Rural Utilities Service (USDA). This is a critical requirement for contractors working on federally funded rural electrification projects, ensuring the cable is vetted for long-term reliability in utility-grade infrastructure.
For 4/0 trunk lines, 133% insulation (220 mils) provides a critical safety buffer. Main feeders often have longer fault-clearing times; the extra TR-XLPE thickness ensures the system can withstand surge stresses significantly better than standard 100% rated cables.
The minimum bending radius for 4/0 STR 15kV URD is approximately 16.6 inches. Per industry standards, the radius is calculated as 12 times the overall diameter of the cable (1.38" x 12). Maintaining this radius is vital during the installation of larger 4/0 feeders to protect the core from mechanical stress.
Yes, 4/0 15kV URD Cable is rated for direct burial or installation in conduits.