Get notified when this product is back in stock
Physical Specifications
Technical Specifications
Packaging & Dimensions:
|
||||||||||||||||||||||||||||||||||
The overall jacket diameter for #2 AWG STR 15kV 133% URD is approximately 1.07 inches. For a single-conductor installation, a 2-inch conduit is standard. For a triplex configuration (three cables), a 3-inch or 3.5-inch conduit is recommended to maintain the NEC-mandated 40% fill capacity.
Note on Conduit Sizing: These recommendations are based on standard NEC 40% fill guidelines for general informational purposes. Because factors such as pull length, total degrees of bends, and pulling tension vary by project, always consult with a licensed electrical engineer or project lead to verify final conduit specifications and ensure local code compliance.
This #2 AWG cable features 10 x #14 AWG solid bare copper neutral wires. These wires are helically applied and uniformly spaced over the insulation shield. This provides 100% (Full) conductivity relative to the aluminum center conductor, which is a critical safety requirement for many single-phase residential primary systems.
15kV Aluminum URD (Underground Residential Distribution) cable is a medium-voltage cable used for primary underground power distribution at 15,000 volts or less. It features an aluminum conductor, solid or stranded, with Tree-Retardant Cross-Linked Polyethylene (TR-XLPE), rated for direct burial or duct installation in wet/dry locations.
RUS Accepted means this cable meets the technical and durability standards set by the Rural Utilities Service (USDA). This designation is vital for contractors working on federally funded rural electrification or utility projects, as it guarantees the cable has been vetted for long-term reliability in utility-grade infrastructure.
The 133% insulation level provides a thicker 220-mil wall of TR-XLPE, compared to the 175-mil wall found on standard 100% rated cables. This extra thickness offers a higher safety margin and superior protection against voltage surges, specifically in systems where fault-clearing times might be slower.
The minimum bending radius for #2 AWG STR 15kV URD is approximately 13 inches. Per industry standards, the radius should be at least 12 times the overall diameter of the cable. Adhering to this limit during installation is critical to avoid mechanical stress on the insulation shield and copper neutrals, which could lead to premature electrical failure.
Yes, 15kV URD Cable is rated for direct burial or installation in conduits.
(833) 268-8644