10/4 Stranded Copper MC Cable W/ Ground

Parent SKU :  MCCUSTR10-4

SKU :  MCCUSTR10-4-250

4 CONDUCTOR + GROUND • COPPER THHN/THWN-2 • INTERLOCKED ARMOR • 600V
Wire Size 10 AWG
Conductor Material Copper
Conductor Type Stranded
Outer Diameter 0.679 In.
Conductor Count 4
Voltage Rating 600V
Ampacity Rating 40
Weight per Foot 0.282 lb

Get Product Details

Get Product Details

10/4 Stranded Copper MC Cable W/ Ground is a heavy-duty 600V Metal-Clad (MC) building wire engineered for 3-phase 4-wire power distribution, 30A commercial equipment feeders, 277V/480V high-bay lighting, and multi-circuit home runs in commercial, industrial, institutional, and multi-residential applications. Constructed with four flexible 10 AWG Class B stranded bare copper conductors, an insulated 10 AWG green ground wire, THHN/THWN-2 insulation, protective binder tape, and an overall aluminum interlocked armor, it delivers exceptional crush resistance while eliminating the high labor costs of pulling wire through conduit.

Key Features & Benefits

  • Labor-Saving Metal-Clad Design: Pre-armored assembly eliminates the time-consuming process of pulling individual conductors through conduit, lowering jobsite labor costs and accelerating project timelines.

  • 3-Phase 4-Wire Power Distribution: Four 10 AWG circuit conductors enable 3-phase wye power runs, 277V/480V high-bay lighting feeders, or dual 30A 120V branch circuits with separate neutrals.

  • High-Flex Stranded Copper: Built with Class B stranded bare copper conductors to provide superior flexibility, easier pulls, and smooth terminations inside junction boxes and panel boards.

  • Dual-Rated THHN/THWN-2 Insulation: High-dielectric PVC insulation with a clear nylon outer skin provides superior heat, flame, moisture, and gasoline/oil resistance rated for 90°C dry applications.

  • Lightweight Aluminum Interlocked Armor: Tough interlocked aluminum armor (AIA) shields internal conductors from physical damage, crushing, and abrasion while maintaining maximum bendability.

  • Integrated Green Ground Conductor: Includes a dedicated 10 AWG green THHN/THWN-2 insulated stranded copper ground conductor for complete circuit safety.

Technical Specifications

Engineering Overview 

  • Application: 3-phase branch, feeder, and distribution circuits in commercial, industrial, institutional, and multi-residential power, lighting, control, and signal systems.

  • Voltage Rating: 600 Volts.

  • Ampacity: 40 Amps @ 90°C (Based on 30°C ambient temperature per NEC Table 310.16; refer to NEC 240.4(D) for overcurrent protection limits; apply derating factors per NEC 310.15(C)(1) when more than three conductors carry current).

  • Conductor Material: Class B stranded soft-drawn bare copper (4 conductors, 10 AWG).

  • Insulation: PVC (0.020" thickness) with clear Nylon jacket (0.004" thickness) (THHN/THWN-2).

  • Grounding Conductor: One 10 AWG green THHN/THWN-2 insulated stranded copper conductor.

  • Phase Identification: White, Black, Red, Blue phase conductors (120V/208V system color code).

  • Armor: Overall lightweight aluminum interlocked armor.

  • Diameter over Armor: 0.679 inches (17.246 mm).

  • Approximate Net Weight: 282 lbs / 1,000 ft.

  • Temperature Rating: -40°C to +90°C Dry.

  • Approvals & Compliance: UL Listed (UL 83, UL 1569, UL 1581), IEEE 1202 Vertical Tray Flame Test (70,000 BTU/hr), ASTM B3 & B8, Federal Spec A-A-59544, NEC Articles 230.43, 300.22, 330, 518.4, 520.5, 530, 545.4, 645. Hazardous Locations: Class I Div. 2, Class II Div. 2, Class III Div. 1 & 2.


** All values are nominal and subject to correction 

See Full Specifications

See Full Specifications

Physical Specifications

Wire Size (AWG/MCM) 10 AWG
Conductor Material Copper
Conductor Type Stranded
Outer Diameter (OD) (in/mm) 0.679 In.
Conductor Count 4
Shield Unshielded
Insulation Type PVC
UL Listing Numbers UL 83, Ul 1569, UL 1581, UL 2556

Technical Specifications

Voltage Rating 600V
Ampacity Rating 40
Submersible No
Temperature Rating 90ºC
Standards UL Standards 83, 1569, 1581 & 2556
IEEE 1202 vertical tray flame test, 70, 000 BTU/hr
ASTM B3, B258
NEC Articles 300.22, 330, 518.4, 520.5, 530, 545.4 & 645
Class I Div. 2, Class II Div. 2 and Class III Div. 1 Div. 2 for hazardous locations
Federal Specification A-A59544
Miscellaneous Information All values are nominal and subject to correction.
RoHS Compliance Yes

Usage & Installation

Primary ApplicationsCommercial Branch Circuits, Industrial Facilities, Lighting Systems, Residential Multi-Family Housing, Environmental Air Spaces, Exposed and Concealed Wiring
Common Uses
  • Drop Ceiling Runs
  • Wall Cavity Fishing
  • Surface-Mounted Power
  • HVAC Equipment Connections
  • Appliance Hookups
  • Data Centers

Packaging & Dimensions:

Weight per Foot 0.282 lb

Real World Applications

Real World Applications

  • 3-Phase 30A Equipment Runs: Powers 120V/208V 3-phase wye or 277V/480V commercial HVAC equipment, heavy motors, large air compressors, and industrial machinery.
  • High-Bay Commercial Lighting: Ideal for running 277V 3-phase lighting circuits in warehouses, big-box retail stores, and manufacturing plants.
  • Exposed & Concealed Wiring: Approved for exposed runs mounted to building structural members or concealed runs installed above dropped ceilings and inside drywall stud cavities.
  • Places of Assembly: Fully compliant with NEC rules for places of assembly accommodating 100 or more people, including auditoriums, theaters, studios, and commercial facilities.
  • Environmental Air Spaces (Plenums): Safe for installation in environmental air-handling spaces and plenums per NEC Article 300.22.
  • Approved Cable Trays & Raceways: Ideal for distribution routing in approved industrial cable trays, open ladder racks, and wireways without requiring rigid metal conduit.

Real-world application examples are provided for educational and general planning purposes only. Project requirements vary based on system design, environmental factors, and local codes. Buyers and specifiers are responsible for verifying that all materials meet exact job specifications and comply with NEC and local electrical regulations. Always consult with a licensed electrician prior to installation.

Shipping and Returns

Shipping and Returns

General Shipping Information

In-stock orders placed before 3pm EST typically ship within 1-2 business days. Our business days are Monday through Friday; we do not process orders on Saturday, Sunday, or major US Holidays.

You will receive an e-mail with a tracking number within 1-2 business days from the time its shipped. You will also be able to view your order status and tracking numbers in your account order history.

Expedited Shipping

Expedited shipments are delivered Monday-Friday except on US Holidays. The order must be placed before 12pm CST to ship same day ( Mon-Fri Only).

Returns

You have 30 days from the day you receive the item to contact us for a return. Returns are subject to a 30% Restocking Fee.

Please contact us at help@wireamerica.com to request a return authorization. Have your order number or name the order was placed with ready and we will email you an RMA (return) number and instructions for return. Currently, we do not offer exchanges. A new order must be placed if you need a different item. If you provide the new order number at the time of your return request, the restocking fee may be lowered.

Orders on any items with a material value of $50 or less are non-returnable.

10/4 Stranded Copper MC Cable W/ Ground

Parent SKU :  MCCUSTR10-4

SKU :  MCCUSTR10-4-250

4 CONDUCTOR + GROUND • COPPER THHN/THWN-2 • INTERLOCKED ARMOR • 600V
In Stock
Ships in 1-2 days

Parent SKU :  MCCUSTR10-4

SKU :  MCCUSTR10-4-250

$1,288/ea.
$5,100/ea.
Please select an option
Min: 250 ft., Max: 20,000 ft.
Spool (250 ft.)
$1,288.00
Please select an option
Maximum reached, contact us for custom orders
Contact Us
  • Fast Shipping
  • Competitive Pricing
  • Phone Support

Get Product Details

Get Product Details

10/4 Stranded Copper MC Cable W/ Ground is a heavy-duty 600V Metal-Clad (MC) building wire engineered for 3-phase 4-wire power distribution, 30A commercial equipment feeders, 277V/480V high-bay lighting, and multi-circuit home runs in commercial, industrial, institutional, and multi-residential applications. Constructed with four flexible 10 AWG Class B stranded bare copper conductors, an insulated 10 AWG green ground wire, THHN/THWN-2 insulation, protective binder tape, and an overall aluminum interlocked armor, it delivers exceptional crush resistance while eliminating the high labor costs of pulling wire through conduit.

Key Features & Benefits

  • Labor-Saving Metal-Clad Design: Pre-armored assembly eliminates the time-consuming process of pulling individual conductors through conduit, lowering jobsite labor costs and accelerating project timelines.

  • 3-Phase 4-Wire Power Distribution: Four 10 AWG circuit conductors enable 3-phase wye power runs, 277V/480V high-bay lighting feeders, or dual 30A 120V branch circuits with separate neutrals.

  • High-Flex Stranded Copper: Built with Class B stranded bare copper conductors to provide superior flexibility, easier pulls, and smooth terminations inside junction boxes and panel boards.

  • Dual-Rated THHN/THWN-2 Insulation: High-dielectric PVC insulation with a clear nylon outer skin provides superior heat, flame, moisture, and gasoline/oil resistance rated for 90°C dry applications.

  • Lightweight Aluminum Interlocked Armor: Tough interlocked aluminum armor (AIA) shields internal conductors from physical damage, crushing, and abrasion while maintaining maximum bendability.

  • Integrated Green Ground Conductor: Includes a dedicated 10 AWG green THHN/THWN-2 insulated stranded copper ground conductor for complete circuit safety.

Technical Specifications

Engineering Overview 

  • Application: 3-phase branch, feeder, and distribution circuits in commercial, industrial, institutional, and multi-residential power, lighting, control, and signal systems.

  • Voltage Rating: 600 Volts.

  • Ampacity: 40 Amps @ 90°C (Based on 30°C ambient temperature per NEC Table 310.16; refer to NEC 240.4(D) for overcurrent protection limits; apply derating factors per NEC 310.15(C)(1) when more than three conductors carry current).

  • Conductor Material: Class B stranded soft-drawn bare copper (4 conductors, 10 AWG).

  • Insulation: PVC (0.020" thickness) with clear Nylon jacket (0.004" thickness) (THHN/THWN-2).

  • Grounding Conductor: One 10 AWG green THHN/THWN-2 insulated stranded copper conductor.

  • Phase Identification: White, Black, Red, Blue phase conductors (120V/208V system color code).

  • Armor: Overall lightweight aluminum interlocked armor.

  • Diameter over Armor: 0.679 inches (17.246 mm).

  • Approximate Net Weight: 282 lbs / 1,000 ft.

  • Temperature Rating: -40°C to +90°C Dry.

  • Approvals & Compliance: UL Listed (UL 83, UL 1569, UL 1581), IEEE 1202 Vertical Tray Flame Test (70,000 BTU/hr), ASTM B3 & B8, Federal Spec A-A-59544, NEC Articles 230.43, 300.22, 330, 518.4, 520.5, 530, 545.4, 645. Hazardous Locations: Class I Div. 2, Class II Div. 2, Class III Div. 1 & 2.


** All values are nominal and subject to correction 

See Full Specifications

See Full Specifications

Physical Specifications

Wire Size (AWG/MCM) 10 AWG
Conductor Material Copper
Conductor Type Stranded
Outer Diameter (OD) (in/mm) 0.679 In.
Conductor Count 4
Shield Unshielded
Insulation Type PVC
UL Listing Numbers UL 83, Ul 1569, UL 1581, UL 2556

Technical Specifications

Voltage Rating 600V
Ampacity Rating 40
Submersible No
Temperature Rating 90ºC
Standards UL Standards 83, 1569, 1581 & 2556
IEEE 1202 vertical tray flame test, 70, 000 BTU/hr
ASTM B3, B258
NEC Articles 300.22, 330, 518.4, 520.5, 530, 545.4 & 645
Class I Div. 2, Class II Div. 2 and Class III Div. 1 Div. 2 for hazardous locations
Federal Specification A-A59544
Miscellaneous Information All values are nominal and subject to correction.
RoHS Compliance Yes

Usage & Installation

Primary ApplicationsCommercial Branch Circuits, Industrial Facilities, Lighting Systems, Residential Multi-Family Housing, Environmental Air Spaces, Exposed and Concealed Wiring
Common Uses
  • Drop Ceiling Runs
  • Wall Cavity Fishing
  • Surface-Mounted Power
  • HVAC Equipment Connections
  • Appliance Hookups
  • Data Centers

Packaging & Dimensions:

Weight per Foot 0.282 lb

Real World Applications

Real World Applications

  • 3-Phase 30A Equipment Runs: Powers 120V/208V 3-phase wye or 277V/480V commercial HVAC equipment, heavy motors, large air compressors, and industrial machinery.
  • High-Bay Commercial Lighting: Ideal for running 277V 3-phase lighting circuits in warehouses, big-box retail stores, and manufacturing plants.
  • Exposed & Concealed Wiring: Approved for exposed runs mounted to building structural members or concealed runs installed above dropped ceilings and inside drywall stud cavities.
  • Places of Assembly: Fully compliant with NEC rules for places of assembly accommodating 100 or more people, including auditoriums, theaters, studios, and commercial facilities.
  • Environmental Air Spaces (Plenums): Safe for installation in environmental air-handling spaces and plenums per NEC Article 300.22.
  • Approved Cable Trays & Raceways: Ideal for distribution routing in approved industrial cable trays, open ladder racks, and wireways without requiring rigid metal conduit.

Real-world application examples are provided for educational and general planning purposes only. Project requirements vary based on system design, environmental factors, and local codes. Buyers and specifiers are responsible for verifying that all materials meet exact job specifications and comply with NEC and local electrical regulations. Always consult with a licensed electrician prior to installation.

Shipping and Returns

Shipping and Returns

General Shipping Information

In-stock orders placed before 3pm EST typically ship within 1-2 business days. Our business days are Monday through Friday; we do not process orders on Saturday, Sunday, or major US Holidays.

You will receive an e-mail with a tracking number within 1-2 business days from the time its shipped. You will also be able to view your order status and tracking numbers in your account order history.

Expedited Shipping

Expedited shipments are delivered Monday-Friday except on US Holidays. The order must be placed before 12pm CST to ship same day ( Mon-Fri Only).

Returns

You have 30 days from the day you receive the item to contact us for a return. Returns are subject to a 30% Restocking Fee.

Please contact us at help@wireamerica.com to request a return authorization. Have your order number or name the order was placed with ready and we will email you an RMA (return) number and instructions for return. Currently, we do not offer exchanges. A new order must be placed if you need a different item. If you provide the new order number at the time of your return request, the restocking fee may be lowered.

Orders on any items with a material value of $50 or less are non-returnable.

Physical Specifications

Wire Size (AWG/MCM) 10 AWG
Conductor Material Copper
Conductor Type Stranded
Outer Diameter (OD) (in/mm) 0.679 In.
Conductor Count 4
Shield Unshielded
Insulation Type PVC
UL Listing Numbers UL 83, Ul 1569, UL 1581, UL 2556

Technical Specifications

Voltage Rating 600V
Ampacity Rating 40
Submersible No
Temperature Rating 90ºC
Standards UL Standards 83, 1569, 1581 & 2556
IEEE 1202 vertical tray flame test, 70, 000 BTU/hr
ASTM B3, B258
NEC Articles 300.22, 330, 518.4, 520.5, 530, 545.4 & 645
Class I Div. 2, Class II Div. 2 and Class III Div. 1 Div. 2 for hazardous locations
Federal Specification A-A59544
Miscellaneous Information All values are nominal and subject to correction.
RoHS Compliance Yes

Usage & Installation:

Primary ApplicationsCommercial Branch Circuits, Industrial Facilities, Lighting Systems, Residential Multi-Family Housing, Environmental Air Spaces, Exposed and Concealed Wiring
Common Uses
  • Drop Ceiling Runs
  • Wall Cavity Fishing
  • Surface-Mounted Power
  • HVAC Equipment Connections
  • Appliance Hookups
  • Data Centers

Packaging & Dimensions:

Weight per Foot 0.282 lb

Have Questions?

Call Us. Icon

Call Us.

(833) 268-8644

Email Us

10/4 Stranded Copper MC Cable is a 600V metal-clad cable used for 3-phase 4-wire power distribution, 30A commercial equipment feeders, and 277V/480V high-bay lighting runs. It features four 10 AWG stranded copper circuit conductors (Black/Red/Blue/White) and one 10 AWG green insulated ground enclosed in an aluminum interlocked armor.

10/3 MC Cable contains three current-carrying conductors (Black/Red/White) plus ground for single-phase 120V/240V or 3-phase 3-wire runs. 10/4 MC Cable adds a fourth conductor (Blue), enabling full 3-phase 4-wire wye wiring (Black/Red/Blue/White) or running two separate 30A 120V circuits with dedicated neutrals in a single cable pull.

Under NEC Section 240.4(D), 10 AWG copper conductors are generally restricted to a maximum overcurrent protection rating of 30 Amps for standard branch circuits, despite having a higher raw conductor thermal ampacity rating (40A at 90°C).

Yes, in certain installations. When all four conductors are carrying current simultaneously (such as two single-phase branch circuits sharing a single cable sheath), NEC Table 310.15(C)(1) requires an 80% adjustment factor on the conductor ampacity rating.

Yes. Because the aluminum interlocked armor provides continuous mechanical protection, MC cable is approved under NEC Article 330 to be installed directly inside walls, exposed across ceilings, or laid in cable trays without pulling through pipe or conduit.

Standard 10/4 MC cable with aluminum interlocked armor is designed for dry indoor applications (rated 90°C Dry). For direct burial or wet outdoor environments, a PVC-jacketed MC cable (PVC over armor) or liquid-tight raceway system is required.