2-2-2-2 Quadruplex Aluminum Direct Burial Cable, Wittenberg URD

Prent SKU:WIT-4URD

SKU:WIT-4URD-100

600 VOLT XLPE JACKET, SUNLIGHT RESISTANT. URD.
Wire Size 2 AWG
Conductor Material Aluminum
Conductor Type Stranded
Outer Diameter 0.97 in. / 24.638 mm
Conductor Count 4
Voltage Rating 600
Ampacity Rating 155

Product Details

Product Details
APPLICATION:
Quadruplex Aluminum 600V URD cable is designed for use in secondary distribution circuits, where installed in duct or direct burial applications. This cable has 4 conductors. Maximum operating temperature is not to exceed 90°C in wet and dry locations. Voltage rating is 600 volts.

CONDUCTOR:
Concentric stranded or compressed 1350-H19 series aluminum conductor.

INSULATION:
Black sunlight resistant cross-linked polyethylene (XLP) insulation.

AMP RATING:
Duct / Conduit - 115 Amps
Direct Bury - 155 Amps



All values are nominal and subject to correction. *Not RUS accepted size **Ampacity: 90°C conductor temperature, 20°C ambient temperature, RHO 90, 100% load factor. Single and Quadruplex based on 3/C. Neutral wire carries unbalanced load only. Reference NEC article 310.15 for NEC installations.

Full Specifications

Full Specifications

Physical Specifications

Wire Size (AWG/MCM) 2 AWG
Conductor Material Aluminum
Conductor Type Stranded
Strand Count 7
Outer Diameter (OD) (in/mm) 0.97 in. / 24.638 mm
Jacket Type XLPE
Conductor Count 4
Shield Unshielded
Insulation Type (XLPE) Cross-Linked Polyethylene

Technical Specifications

Voltage Rating 600
Ampacity Rating 155
Direct Burial Rating Yes
Submersible No
Flexibility Rating Medium
Sunlight Resistance Rating Yes
Temperature Rating 90ºC
Standards ASTM B-230 Aluminum 1350-H19 Wire for Electrical Purposes
ASTM B-231 Concentric-Lay-Stranded Aluminum 1350 Conductors
ASTM B-609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
ASTM B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction
ICEA S-105-692 600 Volt Single Layer Thermoset Insulated Utility Underground Distribution Cables
Federal Specification A-A-59544A
UL 854 Service-Entrance Cables
Sunlight Resistant
RUS Accepted
Miscellaneous Information All values are nominal and subject to correction. *Not RUS accepted size **Ampacity: 90°C conductor temperature, 20°C ambient temperature, RHO 90, 100% load factor. Single and Quadruplex based on 3/C. Neutral wire carries unbalanced load only. Reference NEC article 310.15 for NEC installations.

Usage & Installation

Primary ApplicationsUnderground Secondary Power Distribution
Common Uses
  • Single-family homes
  • Apartment complexes
  • Farms
  • Smaller commercial buildings.

Packaging & Dimensions:

Weight per Foot 0.389 lb

Shipping and Returns

Shipping and Returns

General Shipping Information

In-stock orders placed before 3pm EST typically ship within 1-2 business days. Our business days are Monday through Friday; we do not process orders on Saturday, Sunday, or major US Holidays.

You will receive an e-mail with a tracking number within 1-2 business days from the time its shipped. You will also be able to view your order status and tracking numbers in your account order history.

Expedited Shipping

Expedited shipments are delivered Monday-Friday except on US Holidays. The order must be placed before 12pm CST to ship same day ( Mon-Fri Only).

Returns

You have 30 days from the day you receive the item to contact us for a return. Returns are subject to a 30% Restocking Fee.

Please contact us at help@wireamerica.com to request a return authorization. Have your order number or name the order was placed with ready and we will email you an RMA (return) number and instructions for return. Currently, we do not offer exchanges. A new order must be placed if you need a different item. If you provide the new order number at the time of your return request, the restocking fee may be lowered.

Orders on any items with a material value of $50 or less are non-returnable.

Aluminum Quadruplex Direct Burial URD

Wire America | Wire Flexibility Series

This video shows the flexibility, size, jacket detail, conductor material and stranding of the Dyke 2 Gauge, 4 Conductor Quadruplex URD, Aluminum Direct Burial Cable.

2-2-2-2 Quadruplex Aluminum Direct Burial Cable, Wittenberg URD

Prent SKU:WIT-4URD

SKU:WIT-4URD-100

600 VOLT XLPE JACKET, SUNLIGHT RESISTANT. URD.
In Stock
Ships in 1-2 days

Prent SKU:WIT-4URD

SKU:WIT-4URD-100

$1.96/ft
$1.94/ft
$1.94/ft
$1.94/ft
$2.01/ft
Please select an option
  • Fast Shipping
  • Competitive Pricing
  • Phone Support

Product Details

Product Details
APPLICATION:
Quadruplex Aluminum 600V URD cable is designed for use in secondary distribution circuits, where installed in duct or direct burial applications. This cable has 4 conductors. Maximum operating temperature is not to exceed 90°C in wet and dry locations. Voltage rating is 600 volts.

CONDUCTOR:
Concentric stranded or compressed 1350-H19 series aluminum conductor.

INSULATION:
Black sunlight resistant cross-linked polyethylene (XLP) insulation.

AMP RATING:
Duct / Conduit - 115 Amps
Direct Bury - 155 Amps



All values are nominal and subject to correction. *Not RUS accepted size **Ampacity: 90°C conductor temperature, 20°C ambient temperature, RHO 90, 100% load factor. Single and Quadruplex based on 3/C. Neutral wire carries unbalanced load only. Reference NEC article 310.15 for NEC installations.

Full Specifications

Full Specifications

Physical Specifications

Wire Size (AWG/MCM) 2 AWG
Conductor Material Aluminum
Conductor Type Stranded
Strand Count 7
Outer Diameter (OD) (in/mm) 0.97 in. / 24.638 mm
Jacket Type XLPE
Conductor Count 4
Shield Unshielded
Insulation Type (XLPE) Cross-Linked Polyethylene

Technical Specifications

Voltage Rating 600
Ampacity Rating 155
Direct Burial Rating Yes
Submersible No
Flexibility Rating Medium
Sunlight Resistance Rating Yes
Temperature Rating 90ºC
Standards ASTM B-230 Aluminum 1350-H19 Wire for Electrical Purposes
ASTM B-231 Concentric-Lay-Stranded Aluminum 1350 Conductors
ASTM B-609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
ASTM B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction
ICEA S-105-692 600 Volt Single Layer Thermoset Insulated Utility Underground Distribution Cables
Federal Specification A-A-59544A
UL 854 Service-Entrance Cables
Sunlight Resistant
RUS Accepted
Miscellaneous Information All values are nominal and subject to correction. *Not RUS accepted size **Ampacity: 90°C conductor temperature, 20°C ambient temperature, RHO 90, 100% load factor. Single and Quadruplex based on 3/C. Neutral wire carries unbalanced load only. Reference NEC article 310.15 for NEC installations.

Usage & Installation

Primary ApplicationsUnderground Secondary Power Distribution
Common Uses
  • Single-family homes
  • Apartment complexes
  • Farms
  • Smaller commercial buildings.

Packaging & Dimensions:

Weight per Foot 0.389 lb

Shipping and Returns

Shipping and Returns

General Shipping Information

In-stock orders placed before 3pm EST typically ship within 1-2 business days. Our business days are Monday through Friday; we do not process orders on Saturday, Sunday, or major US Holidays.

You will receive an e-mail with a tracking number within 1-2 business days from the time its shipped. You will also be able to view your order status and tracking numbers in your account order history.

Expedited Shipping

Expedited shipments are delivered Monday-Friday except on US Holidays. The order must be placed before 12pm CST to ship same day ( Mon-Fri Only).

Returns

You have 30 days from the day you receive the item to contact us for a return. Returns are subject to a 30% Restocking Fee.

Please contact us at help@wireamerica.com to request a return authorization. Have your order number or name the order was placed with ready and we will email you an RMA (return) number and instructions for return. Currently, we do not offer exchanges. A new order must be placed if you need a different item. If you provide the new order number at the time of your return request, the restocking fee may be lowered.

Orders on any items with a material value of $50 or less are non-returnable.

Aluminum Quadruplex Direct Burial URD

Wire America | Wire Flexibility Series

This video shows the flexibility, size, jacket detail, conductor material and stranding of the Dyke 2 Gauge, 4 Conductor Quadruplex URD, Aluminum Direct Burial Cable.

Physical Specifications

Wire Size (AWG/MCM) 2 AWG
Conductor Material Aluminum
Conductor Type Stranded
Strand Count 7
Outer Diameter (OD) (in/mm) 0.97 in. / 24.638 mm
Jacket Type XLPE
Conductor Count 4
Shield Unshielded
Insulation Type (XLPE) Cross-Linked Polyethylene

Technical Specifications

Voltage Rating 600
Ampacity Rating 155
Direct Burial Rating Yes
Submersible No
Flexibility Rating Medium
Sunlight Resistance Rating Yes
Temperature Rating 90ºC
Standards ASTM B-230 Aluminum 1350-H19 Wire for Electrical Purposes
ASTM B-231 Concentric-Lay-Stranded Aluminum 1350 Conductors
ASTM B-609 Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
ASTM B-901 Compressed Round Stranded Aluminum Conductors Using Single Input Wire Construction
ICEA S-105-692 600 Volt Single Layer Thermoset Insulated Utility Underground Distribution Cables
Federal Specification A-A-59544A
UL 854 Service-Entrance Cables
Sunlight Resistant
RUS Accepted
Miscellaneous Information All values are nominal and subject to correction. *Not RUS accepted size **Ampacity: 90°C conductor temperature, 20°C ambient temperature, RHO 90, 100% load factor. Single and Quadruplex based on 3/C. Neutral wire carries unbalanced load only. Reference NEC article 310.15 for NEC installations.

Usage & Installation:

Primary ApplicationsUnderground Secondary Power Distribution
Common Uses
  • Single-family homes
  • Apartment complexes
  • Farms
  • Smaller commercial buildings.

Packaging & Dimensions:

Weight per Foot 0.389 lb

Have Questions?

We've got answers.

Call Us.

(833) 268-8644

Contact Support
AWG, or American Wire Gauge, is the standard system used primarily in North America to measure the diameter of electrical conductors. This system is critical because a wire's size directly impacts its electrical resistance and how much current (ampacity) it can safely carry. A key principle is that the smaller the AWG number, the larger the wire's diameter; for instance, 12 AWG is thicker and can carry more current than 14 AWG. Sizes beyond 0 AWG are referred to as "aught" (e.g., 1/0, 2/0). Selecting the correct AWG is essential for safe electrical installations, preventing overheating, and minimizing voltage drop.
Voltage drop is the natural reduction in electrical potential that occurs as current travels through a circuit, from the power source to a device. This happens because all wires inherently have resistance, which converts some electrical energy into heat, leading to a loss of voltage. While minor voltage drop is normal, excessive amounts can cause problems like dimming lights, slow or overheating motors, and erratic electronic behavior. It can also lead to higher energy consumption and, in severe cases, create safety hazards due to overheating wires. Key factors influencing voltage drop include the wire's length and thickness (gauge), the amount of current flowing through it, and the quality of electrical connections.
In electrical wiring, amps (amperes) measure the rate of electrical current flow. Think of it as the volume of electricity moving through the wire at any given time. Crucially, every electrical wire has an ampacity rating, which is the maximum current it can safely carry continuously without overheating. Exceeding a wire's ampacity can lead to insulation damage and fire hazards, highlighting why proper wire sizing based on expected amperage is vital for safe electrical systems.
A wire's ampacity, or its safe current-carrying capacity, changes with temperature primarily because of two factors. First, the electrical resistance of copper and aluminum wires increases as they get hotter, causing them to generate more heat when current flows. Second, every wire's insulation has a maximum temperature limit; exceeding this can cause degradation and safety hazards. Therefore, in hotter environments, a wire must carry less current to avoid exceeding its insulation's temperature rating. This ensures the wire remains safe and functional, preventing overheating and potential failures.
We aim to provide authentic, precise images of each wire; however, with various product variations, it can be challenging. In such instances, we focus on showcasing the fundamental design. Always refer to the product specifications rather than relying solely on images.